Protecting a wind or solar farm is a different problem from protecting a single building. Sites run to several square kilometres, turbines and arrays are dispersed, the ground is often rock or desert, and after commissioning almost nobody is on site. On ground like that the question is not "fit a device" but "how many points, where, and how is coverage calculated".
Two site types, two risk profiles
Wind turbines concentrate risk in three places: the blades, where composite laminates delaminate, crack and erode the receptors after a strike; the pitch and yaw control electronics in the nacelle, with long cable runs and difficult access; and the earthing path through tower and foundation. The wind industry generally works to IEC 61400-24, Lightning protection for wind turbines, which sets requirements separately for blades, nacelle, electrical systems and earthing.
Solar farms spread risk more widely: module frames and mounting structures form a large metallic body with inconsistent bonding, the DC side runs at high voltage with combiner boxes and inverter ports as surge entry points, and the substation and control building concentrate the communication and control circuits. Such sites are normally designed to IEC 62305 together with GB 50057 and grid-connection requirements, with bonding and port protection as the priority.
Layout logic: overlap first, no holes
The first rule on a large site is not "cover the boundary" but "cover continuously". Adjacent coverage circles must overlap, because the site is continuous and protection cannot have gaps. The upper panel of Figure 1 shows a typical arrangement: devices placed along the main equipment areas, circles lapping one another, with turbines, array blocks and the substation all inside coverage.
Three checks drive the layout: whether the mounting point is higher than everything it protects (control building roofs, transformer plinths and combiner supports are often lower than assumed); how much of the horizontal radius remains at the target height, since the radius is a value at the device, not at ground level; and whether any structure beyond the boundary is taller.
Shadowing: check it in section, not on the map
The lower panel of Figure 1 shows the point most often missed: a taller structure cuts a shadow out of the protected volume. The turbine tower there is clearly taller than the control building, and the ground behind it is outside the coverage of the device on that roof — if a transformer or generator shed sits in that patch, it is unprotected.
The correct method is point-by-point on a section drawing: draw the protected sphere about the device, mark every region the sphere cannot reach, then decide whether to add a point, raise the mounting height, or protect the local area by other means. Declaring "full coverage" from a circle on a map is the classic error on projects of this type.
Earthing on rock and desert sites
Farms are often built on ridges, desert or bedrock where soil resistivity runs into the thousands of ohm-metres. The design priorities there are:
- Trade area for resistance. A horizontal grid works better than a deep well; where the site has open ground, extend the grid.
- Parallel electrodes with adequate spacing. Keep spacing at 1.5 to 2 times the electrode length so electrodes do not shield one another.
- Local soil replacement and resistance-reducing materials around foundation and substation electrodes, chosen for long-term stability.
- Bonding before low resistance. Bonding between turbines, transformer plinths, collector lines and the substation often matters more than a single resistance reading.
Measurement methods and acceptance data are covered in the earthing and bonding note.
Knowing whether a strike happened
Inspection cycles on farms are long, and a fault usually surfaces as "one turbine lost communications" or "a combiner box burned". A Storm 7 monitoring system at key points records field activity and events in the protected area; combined with drone inspection and annual earth-resistance measurement it turns "suspected strike" into an archived event record — useful both for insurance claims and for warranty discussions.
Ask for a site layout
Send the site plan, coordinates and heights of turbines and major equipment, the positions of substation and control building, and soil resistivity data. We will return device positions and model recommendations based on protection radius, with a shadowing note and a supporting earthing list. Submit your requirement here, or write to sales@malinsmarine.com.