The most glossed-over number in lightning protection design is "protection radius". A radius goes on the drawing, a circle is drawn at acceptance, and the loop looks closed — except that the three methods used to derive that radius do not produce the same volume. Knowing which method is in play matters more than remembering the number.
Method one: rolling sphere
The rolling sphere is the core method of IEC 62305-3 and GB 50057. A sphere of a specified radius — set by the protection level, roughly 20 m for class I, 30 m for II, 45 m for III and 60 m for IV — is rolled over the structure. Any part the sphere can reach without touching an air terminal is unprotected. Physically, the radius represents the shortest leader the air-termination system can intercept.
The result is three-dimensional, not a flat circle: the taller the structure, the smaller the horizontal area a given terminal covers, and the sides must be checked separately. Most mistakes in submittals come from treating a radius as a plan-view circle.
Method two: protection angle
The protection angle defines coverage as a cone opening downward from the terminal tip; the angle varies with protection level and terminal height. It is quick to apply on regular buildings, but the standards limit its use on slender tall structures such as chimneys and masts, and at the tops of high-rise buildings.
Method three: a declared device radius
A field-compensating device does not intercept leaders; it suppresses the field inside its protected volume. Manufacturers therefore declare a protection radius — a geometric property of a sphere about the device, usually extended cylindrically below it. The CMCE range declares 25 m, 55 m and 120 m, with 120 m being the upper capability of large models such as the TWIN MAX V8, validated in laboratory testing at field strengths in the 840 kV/m class.
Two cautions apply when using a declared radius. First, vertical coverage counts as much as horizontal: the device must stand above the highest protected point to complete the sphere. Second, shadowing: taller neighbouring structures cut into the protected volume, so coverage must be checked point by point rather than asserted with a circle.
How the codes compare
- IEC 62305-3: rolling sphere as the primary method, with protection angle and mesh as alternatives; risk assessment under 62305-2 comes before design.
- NFPA 780: air-termination layout combined with the rolling sphere, with dedicated chapters for flammable liquid tanks.
- GB 50057-2010: rolling-sphere radius set by building class, method aligned with IEC.
- UL 96A / UL 96: the North American certification scheme for air terminals and fittings; some CMCE models carry the relevant listings, which simplifies submittals on North American projects.
The three questions that come up in review
First, a declared radius applied to the top of a tall structure without checking vertical coverage. Second, adjacent devices whose coverage is never checked for overlap, leaving a hole in the middle of a tank group. Third, missing earthing and bonding data — the most accurate radius cannot support a conclusion if the earth path is undocumented. Submit a three-dimensional coverage sketch, a shadowing note and measured earthing values together with the drawings.
Get the calculation checked
Send structure heights, plan outlines, the area to be covered and the code enforced locally. We will return a coverage calculation note for the method in use, together with the device layout. Submit drawings here, or write to sales@malinsmarine.com.